Uponor Ecoflex VIP Thermo Single & Twin

Description

  1. Uponor Ecoflex VIP Thermo  Single & Twin

Thermo VIP Single is suitable for applications where heat loss needs to be at a minimum but with all the benefits of the existing Thermo system.



Pipe Type & Size Pipe Code
Rubber End-Cap WIPEX Coupling
Ecoflex VIP Thermo Single 40/140 1095714 1018314 1018330
Ecoflex VIP Thermo Single 50/140 1095715 1018314 1018330
Ecoflex VIP Thermo Single 63/140 1095716 1018314 1018332
Ecoflex VIP Thermo Single 75/140 1095717 1095801 1018333
Ecoflex VIP Thermo Single 90/140 1095718 1018311 1018334
Ecoflex VIP Thermo Single 110/175 1095719 1018311 1018335
Ecoflex VIP Thermo Single 125/200 1095720 1067757 1078368
Ecoflex VIP Thermo Single 140/200 1121643 1121645 1121647
Ecoflex VIP Thermo Twin 2x25/140 1118580 1018245 1018328
Ecoflex VIP Thermo Twin 2x32/140 1118581 1018245 1018329
Ecoflex VIP Thermo Twin 2x40/175 1118582 1018309 1018330
Ecoflex VIP Thermo Twin 2x50/175 1118583 1018308 1018331
Ecoflex VIP Thermo Twin 22x63/20 1118584 1018307 1018332
Ecoflex VIP Thermo Twin 2x75/250 1118585 1088979 1018333
This product is cut-to-order. Returns for bespoke/made to or cut to order are not accepted. Please ensure that all lengths and the correct pipe are ordered. Please refer to the Uponor Ecoflex Pre-Insulated Pipe technical guide PDF for full details

Technical Specifications

  • Thermo VIP Single

Type
Medium pipe, do1 x s1 [mm]
Jacket pipe do [mm]
Bending radius [m]
Weight [kg/m]
Volume medium pipe [l/m]
Coil length [m]
U-Value [W/ m·K]
109571440 x 3,7
140
0,35
1,67
0,83
200
0,098
109571550 x 4,6
140
0,40
1,93
1,31
200
0,115
109571663 x 5,8
140
0,50
2,35
2,07
200
0,138
109571775 x 6,8
140
0,60
2,73
2,96
200
0,163
109571890 x 8,2
175
0,70
4,00
4,25
200
0,166
1095719110 x 10,0
175
0,90
5,08
6,36
200
0,209
1095720125 x 11,4
200
1,30
6,65
8,20
200
0,215
1121643140 x 12,7
200
1,70
8,52
10,31
200
0,253

Thermo VIP Twin

Type
Medium pipe, do1 x s1 [mm]
Medium pipe, do2 x s2 [mm]
Jacket pipe do [mm]
Bending radius [m]
Weight [kg/m
Volume medium pipe [l/m]
Coil length [m]
U-Value [W/ m·K]
111858025 x 2,3
25 x 2,3
140
0,40
0,40
0,40
200
0,122
111858132 x 2,9
32 x 2,9
140
0,50
0,40
0,40
200
0,145
111858240 x 3,7
40 x 3,7
175
0,80
0,40
0,40
200
0,153
111858350 x 4,6
50 x 4,6
175
0,90
0,40
0,40
200
0,185
111858463 x 5,8
63 x 5,8
200
1,20
0,40
0,40
200
0,212
111858575 x 6,8
75 x 6,8
250
1,40
0,40
0,40
200
0,222